Skip to content
GRIDSPEC
Verified Engineering Spec • NEC 2026 / UL 9540

Can the Anker SOLIX F2000 (PowerHouse 767) Run a Tesla Model Y (Mobile Connector 32A)?

Live runtime simulator, solar recharge calculator and NEC / IEC breaker & cable schematic for the Anker SOLIX F2000 (PowerHouse 767) (2,048 Wh) paired with the Tesla Model Y (Mobile Connector 32A).

Configure your system

800 W
25 ft (7.6 m)
100%
Source outlets
NEMA TT-30R / 5-20R
Load connection
NEMA 14-50P
EV range rate
≈ 24 mi (39 km) of range per hour of charging
Compatible 240V Alternative

Tesla Powerwall 3 (11,500 W, 240V split-phase output) runs this load at 67% utilization.

As an Amazon Associate, we earn from qualifying purchases.

240V Split-Phase Required

Tesla Model Y (Mobile Connector 32A) needs a 240V split-phase circuit — the Anker SOLIX F2000 (PowerHouse 767) only outputs 120V.

Wattage also falls short: 7,680 W running / 7,680 W surge vs 2,400 W / 3,600 W.

Continuous load
320%
Runtime (no sun)
—
Needs 240V output
Solar recharge
3.2 hrs
0.7 sun-days at 800 W
Min. copper wire
8 AWG
0.5% drop @ 25 ft
Overcurrent device
40A Breaker
32.0A load × 1.25 = 40.0A
Live schematic & breaker sizing diagram 120/240V Split-Phase • NEC 125% Rule
SOLAR PV INPUT 800 W PV MC4 / XT60 · MPPT POWER SOURCE / INVERTER Anker SOLIX F2000 (PowerHouse 767) 2,048 Wh • 2,400 W 3,600 W surge • 120V 320% load 40A OCPD 8 AWG Cu 32.0A @ 240V CONNECTED LOAD Tesla Model Y (Mobile Connector 32A) 7,680 W running 7,680 W surge 240V load

Engineering report · reviewed against NEC 2026 & BS 7671:2018+A2

Engineering Breakdown: Running a Tesla Model Y (Mobile Connector 32A) on the Anker SOLIX F2000 (PowerHouse 767)

US/NA: 240V Split-Phase Required UK/EU/AU: Continuous Overload 320% inverter utilization

When pairing the Anker SOLIX F2000 (PowerHouse 767) (2,048 Wh LiFePO4 capacity, 2,400 W continuous, 3,600 W surge) with a Tesla Model Y (Mobile Connector 32A) (7,680 W running, 7,680 W starting surge), the system operates at 320% of continuous inverter capacity on a 240 V North American circuit and 307% on a 230 V UK/EU/AU circuit. Our North American verdict is 240V Split-Phase Required, so the runtime figures below are theoretical battery-energy values only. Wiring the connection over a 25 ft run calls for a 40 A breaker and 8 AWG copper, terminated at a NEMA 14-50P connection.

1. Compatibility Verdict & Inverter Load Utilization

In North American mode the Tesla Model Y (Mobile Connector 32A) loads the Anker SOLIX F2000 (PowerHouse 767)'s inverter to 320% of its 2,400 W continuous rating and 213% of its 3,600 W surge rating. The blocking issue is voltage, not just wattage: the load requires a 240 V split-phase supply while this unit outputs 120 V only. The leanest compatible alternative in our database is the Tesla Powerwall 3.

CheckLoad requiresAnker SOLIX F2000 providesUS/NAUK/EU/AU
Continuous output 7,680 W (7,360 W @ 230V) 2,400 W Fail Fail
Start-up surge 7,680 W 3,600 W Fail Fail
Voltage 240 V / 230 V 120 V / 230 V Fail Pass
Connection NEMA 14-50P NEMA TT-30R / 5-20R UK/EU/AU: Type 2 EVSE · IEC 60309 32A Commando

An EVSE is a constant-current device: the vehicle draws exactly the current advertised by the J1772/NACS pilot signal, so the 7,680 W figure is both the running load and the start-up load — there is no motor inrush. That makes the calculation unusually clean. Because this charging profile is 240 V, the vehicle will not draw power from a 120 V-only receptacle at this current; the portable connector would need a Level 1 adapter and a 12 A limit instead. A full battery delivers about 1.6 kWh into the pack after inverter and on-board charger losses, worth roughly 5 miles (9 km) of driving at 3.5 mi/kWh.

As a portable power station, the Anker SOLIX F2000 (PowerHouse 767) integrates the LiFePO4 battery, inverter, MPPT solar controller and AC outlets in one chassis, so it can be wheeled to the load or connected to a transfer switch through its NEMA TT-30R / 5-20R outlet.

Compatible alternative: the Tesla Powerwall 3 with the Tesla Model Y (Mobile Connector 32A) report shows the full sizing for a unit that passes all three checks.

2. Real-World Runtime by Duty Cycle

Nameplate capacity is not usable capacity. DC-to-AC conversion, battery management overhead and cell protection reduce the 2,048 Wh rating to about 1,741 Wh of deliverable AC energy (85% system efficiency). EV charging runs at a fixed current, so the 100% row is the realistic figure; lower rows apply only if you schedule charging in intervals.

Runtime (h) = (2,048 Wh × 0.85) ÷ (7,680 W × duty cycle)
Duty cycleAverage drawRuntime (no solar)Energy per 24 h
25% 1,920 W 54 min 46.1 kWh
50% 3,840 W 27 min 92.2 kWh
65% 4,992 W 21 min 119.8 kWh
100% 7,680 W 14 min 184.3 kWh

Even at a 50% duty cycle the battery lasts 27 min, so plan on solar, grid or generator recharging for anything longer than an evening outage. Because the inverter cannot actually run this load in North American mode, treat these numbers as an energy-budget reference for a compatible inverter of the same capacity.

3. NEC 125% Breaker & Copper Wire Gauge Sizing

NEC 210.19(A) and 210.20(A) require conductors and overcurrent devices for continuous loads — anything running three hours or more, which includes EV charging and HVAC — to be rated at 125% of the load current. For this pairing: 7,680 W ÷ 240 V = 32.0 A, × 1.25 = 40.0 A, which rounds up to the next standard NEC 240.6 size of 40 A. The conductor must be protected by that breaker (75 °C ampacity at least 40 A) and keep round-trip voltage drop at or below 3%, so longer runs are upsized.

Breaker ≥ (7,680 W ÷ 240 V) × 1.25 = 40.0 A → 40 A
Voltage drop % = (2 × L × I × R) ÷ V × 100

North America (NEC, THHN copper, 75 °C)

One-way distanceBreakerMin. copperVoltage dropNote
25 ft (7.6 m) 40 A 8 AWG 0.51% Sized by ampacity
50 ft (15.2 m) 40 A 8 AWG 1.02% Sized by ampacity
75 ft (22.9 m) 40 A 8 AWG 1.53% Sized by ampacity
100 ft (30.5 m) 40 A 8 AWG 2.04% Sized by ampacity

UK / EU / Australia (IEC 60364 / BS 7671, PVC copper, method C)

IEC-based codes size protection by design current rather than a blanket 125% multiplier: Ib ≤ In ≤ Iz. At 230 V the load draws 32.0 A (the EVSE's 32 A pilot current at 230 V), so a 32 A Type B/C MCB with RCD protection applies. In the UK, BS 7671 Section 722 additionally requires a dedicated circuit and Type A or Type B RCD for EV charge points.

One-way distanceMCBMin. cableVoltage drop
7.5 m (25 ft) 32 A 4.0 mm² 0.96%
15 m (49 ft) 32 A 4.0 mm² 1.92%
22.5 m (74 ft) 32 A 4.0 mm² 2.89%
30 m (98 ft) 32 A 6.0 mm² 2.57%

Because the current is modest, 8 AWG copper stays within the voltage-drop target all the way to 100 ft.

4. Solar Array Recharge Time Breakdown

The Anker SOLIX F2000 (PowerHouse 767) accepts up to 1,000 W of photovoltaic input. Real arrays rarely deliver nameplate output, so we apply an 80% harvest factor for MPPT conversion, cell temperature and soiling, and convert hours to days using 4.5 peak-sun-hours — a conservative annual average for the US, southern Europe and Australia (UK winters can fall below 1.5).

PV arrayReal harvest0–100% rechargeSun-days @ 4.5 PSHNet with load @ 50%
400 W 320 W 6.4 hrs 1.4 −3,520 W
800 W 640 W 3.2 hrs 0.7 −3,200 W
1,000 W 800 W 2.6 hrs 0.6 −3,040 W

A typical 800 W portable array refills the battery in about 3.2 hrs of strong sun, while maxing out the 1,000 W input cuts that to 2.6 hrs. To fully offset the Tesla Model Y (Mobile Connector 32A) at a 50% duty cycle (3,840 W average) during daylight you need roughly 4,800 W of panels, which exceeds this unit's 1,000 W input limit — solar can slow the drain but not eliminate it.

5. Frequently Asked Questions

Can the Anker SOLIX F2000 (PowerHouse 767) run a Tesla Model Y (Mobile Connector 32A)?

Not reliably in North America — our verdict is "240V Split-Phase Required". The load needs 240 V split-phase power and the Anker SOLIX F2000 (PowerHouse 767) outputs 120 V only. The Tesla Powerwall 3 is a compatible alternative. In UK/EU/AU 230 V mode the verdict is "Continuous Overload".

How many miles of range can the Anker SOLIX F2000 (PowerHouse 767) add to a Tesla Model Y?

A full 2,048 Wh charge delivers about 1.6 kWh to the vehicle battery after inverter (85%) and on-board charger (90%) losses — roughly 5 miles at 3.5 mi/kWh. Charging at this profile is not possible on this unit without reducing current or changing voltage.

What breaker and wire size do I need to connect a Tesla Model Y (Mobile Connector 32A) to the Anker SOLIX F2000 (PowerHouse 767)?

In the US, 7,680 W at 240 V is 32.0 A; applying the NEC 125% continuous-load rule gives 40.0 A, so use a 40 A breaker and 8 AWG copper for runs up to 25 ft (0.5% voltage drop). In 230 V markets the load draws 32.0 A, protected by a 32 A MCB on 4.0 mm² cable for runs up to 7.5 m. Receptacle: NEMA 14-50P (US) or Type 2 EVSE · IEC 60309 32A Commando (UK/EU/AU).

How long does it take to recharge the Anker SOLIX F2000 (PowerHouse 767) with solar panels?

With an 800 W array and an 80% real-world harvest factor, a full recharge takes about 3.2 hrs of peak sun (0.7 days at 4.5 peak-sun-hours). At its maximum 1,000 W solar input it drops to 2.6 hrs.

Methodology & safety note

Specifications come from manufacturer datasheets in our open dataset; ampacity and resistance values follow NEC Table 310.16 and Chapter 9 Table 8, and BS 7671 Appendix 4. Calculations assume copper conductors, 30 °C ambient and no bundling derating. Inverter-to-panel connections require a listed transfer switch or interlock to prevent back-feeding the grid. These results are an engineering estimate, not a substitute for a licensed electrician and local permit. See our methodology and safety disclaimer.

Status dots show the North American verdict: compatible, conditional, not compatible.

Other loads on the Anker SOLIX F2000 (PowerHouse 767)

All 50 loads on the Anker SOLIX F2000 (PowerHouse 767) →

Other power stations for the Tesla Model Y (Mobile Connector 32A)

Compare every source for this load →

More Electric Vehicle Charging on the Anker SOLIX F2000 (PowerHouse 767)