Can the EcoFlow Delta Pro Ultra (1 Inverter + 1 Battery) Run an Antminer S21 ASIC Hydro/Air Miner (240V PDU)?

Live runtime simulator, solar recharge calculator and NEC / IEC breaker & cable schematic for the EcoFlow Delta Pro Ultra (1 Inverter + 1 Battery) (6,144 Wh) paired with the Antminer S21 ASIC Hydro/Air Miner (240V PDU).

Configure your system

800 W
25 ft (7.6 m)
100%
Source outlets
NEMA L14-30R / TT-30R / 5-20R
Load connection
NEMA L6-30P / C19 PDU
Verified Hardware Match

Check current bundle pricing for the EcoFlow Delta Pro Ultra (1 Inverter + 1 Battery) plus a transfer switch kit for this setup.

As an Amazon Associate, we earn from qualifying purchases.

Verified Compatible

EcoFlow Delta Pro Ultra (1 Inverter + 1 Battery) handles 3,500 W continuous and 3,800 W surge with headroom.

3,700 W of continuous capacity left for other circuits.

Continuous load
49%
Runtime (no sun)
1.5 hrs
100% duty · 85% inverter eff.
Solar recharge
9.6 hrs
2.1 sun-days at 800 W
Min. copper wire
12 AWG
0.6% drop @ 25 ft
Overcurrent device
20A Breaker
14.6A load × 1.25 = 18.2A
Live schematic & breaker sizing diagram 120/240V Split-Phase • NEC 125% Rule
SOLAR PV INPUT 800 W PV MC4 / XT60 · MPPT POWER SOURCE / INVERTER EcoFlow Delta Pro Ultra (1 Inverter + 1 Battery) 6,144 Wh • 7,200 W 10,800 W surge • 120/240V 49% load 20A OCPD 12 AWG Cu 14.6A @ 240V CONNECTED LOAD Antminer S21 ASIC Hydro/Air Miner (240V… 3,500 W running 3,800 W surge 240V load

Engineering report · reviewed against NEC 2026 & BS 7671:2018+A2

Engineering Breakdown: Running a Antminer S21 ASIC Hydro/Air Miner (240V PDU) on the EcoFlow Delta Pro Ultra (1 Inverter + 1 Battery)

US/NA: Verified Compatible UK/EU/AU: Verified Compatible 49% inverter utilization

When pairing the EcoFlow Delta Pro Ultra (1 Inverter + 1 Battery) (6,144 Wh LiFePO4 capacity, 7,200 W continuous, 10,800 W surge) with a Antminer S21 ASIC Hydro/Air Miner (240V PDU) (3,500 W running, 3,800 W starting surge), the system operates at 49% of continuous inverter capacity on a 240 V North American circuit and 49% on a 230 V UK/EU/AU circuit. At a 100% duty cycle and 85% inverter efficiency, a full battery delivers roughly 1.5 hrs of off-grid runtime. Wiring the connection over a 25 ft run calls for a 20 A breaker and 12 AWG copper, terminated at a NEMA L6-30P / C19 PDU connection.

1. Compatibility Verdict & Inverter Load Utilization

In North American mode the Antminer S21 ASIC Hydro/Air Miner (240V PDU) loads the EcoFlow Delta Pro Ultra (1 Inverter + 1 Battery)'s inverter to 49% of its 7,200 W continuous rating and 35% of its 10,800 W surge rating. Both figures are under the 80% sustained-load guideline, so this is a comfortable, verified match with 3,700 W of spare capacity for lights, a router or a refrigerator on the same unit.

CheckLoad requiresEcoFlow Delta Pro Ultra providesUS/NAUK/EU/AU
Continuous output 3,500 W 7,200 W Pass Pass
Start-up surge 3,800 W 10,800 W Pass Pass
Voltage 240 V / 230 V 120/240 V / 230 V Pass Pass
Connection NEMA L6-30P / C19 PDU NEMA L14-30R / TT-30R / 5-20R UK/EU/AU: IEC 60309 16A Commando / Schuko 16A

Critical loads value uptime over raw power. At 3,500 W, this equipment is small relative to the EcoFlow Delta Pro Ultra (1 Inverter + 1 Battery)'s 7,200 W inverter, so the deciding factors are runtime, pure-sine output quality and switchover time. Most modern power stations offer UPS or EPS pass-through with a 10–30 ms transfer, which is fast enough for CPAP machines, routers and servers with active-PFC power supplies. For medical devices, always confirm with the device manufacturer and keep a secondary backup plan; for CPAP specifically, a DC adapter can extend runtime by 20–30% by skipping inverter losses.

The EcoFlow Delta Pro Ultra (1 Inverter + 1 Battery) is engineered as a whole-home backup system, typically wired through a smart panel or transfer switch so that selected circuits switch over automatically during an outage.

2. Real-World Runtime by Duty Cycle

Nameplate capacity is not usable capacity. DC-to-AC conversion, battery management overhead and cell protection reduce the 6,144 Wh rating to about 5,222 Wh of deliverable AC energy (85% system efficiency). Duty cycle is the share of each hour the load actually draws its running power — thermostats, pressure switches and intermittent use all lower it.

Runtime (h) = (6,144 Wh × 0.85) ÷ (3,500 W × duty cycle)
Duty cycleAverage drawRuntime (no solar)Energy per 24 h
25% 875 W 6.0 hrs 21.0 kWh
50% 1,750 W 3.0 hrs 42.0 kWh
65% 2,275 W 2.3 hrs 54.6 kWh
100% 3,500 W 1.5 hrs 84.0 kWh

Even at a 50% duty cycle the battery lasts 3.0 hrs, so plan on solar, grid or generator recharging for anything longer than an evening outage.

3. NEC 125% Breaker & Copper Wire Gauge Sizing

NEC 210.19(A) and 210.20(A) require conductors and overcurrent devices for continuous loads — anything running three hours or more, which includes EV charging and HVAC — to be rated at 125% of the load current. For this pairing: 3,500 W ÷ 240 V = 14.6 A, × 1.25 = 18.2 A, which rounds up to the next standard NEC 240.6 size of 20 A. The conductor must be protected by that breaker (75 °C ampacity at least 20 A) and keep round-trip voltage drop at or below 3%, so longer runs are upsized.

Breaker ≥ (3,500 W ÷ 240 V) × 1.25 = 18.2 A → 20 A
Voltage drop % = (2 × L × I × R) ÷ V × 100

North America (NEC, THHN copper, 75 °C)

One-way distanceBreakerMin. copperVoltage dropNote
25 ft (7.6 m) 20 A 12 AWG 0.59% Sized by ampacity
50 ft (15.2 m) 20 A 12 AWG 1.17% Sized by ampacity
75 ft (22.9 m) 20 A 12 AWG 1.76% Sized by ampacity
100 ft (30.5 m) 20 A 12 AWG 2.35% Sized by ampacity

UK / EU / Australia (IEC 60364 / BS 7671, PVC copper, method C)

IEC-based codes size protection by design current rather than a blanket 125% multiplier: Ib ≤ In ≤ Iz. At 230 V the load draws 15.2 A, so a 16 A Type B/C MCB with RCD protection applies. In the UK, BS 7671 Section 722 additionally requires a dedicated circuit and Type A or Type B RCD for EV charge points.

One-way distanceMCBMin. cableVoltage drop
7.5 m (25 ft) 16 A 1.5 mm² 1.20%
15 m (49 ft) 16 A 1.5 mm² 2.40%
22.5 m (74 ft) 16 A 2.5 mm² 2.21%
30 m (98 ft) 16 A 2.5 mm² 2.94%

Because the current is modest, 12 AWG copper stays within the voltage-drop target all the way to 100 ft.

4. Solar Array Recharge Time Breakdown

The EcoFlow Delta Pro Ultra (1 Inverter + 1 Battery) accepts up to 5,600 W of photovoltaic input. Real arrays rarely deliver nameplate output, so we apply an 80% harvest factor for MPPT conversion, cell temperature and soiling, and convert hours to days using 4.5 peak-sun-hours — a conservative annual average for the US, southern Europe and Australia (UK winters can fall below 1.5).

PV arrayReal harvest0–100% rechargeSun-days @ 4.5 PSHNet with load @ 50%
400 W 320 W 19.2 hrs 4.3 −1,430 W
800 W 640 W 9.6 hrs 2.1 −1,110 W
1,600 W 1,280 W 4.8 hrs 1.1 −470 W
3,000 W 2,400 W 2.6 hrs 0.6 +650 W
5,600 W 4,480 W 1.4 hrs 0.3 +2,730 W

A typical 800 W portable array refills the battery in about 9.6 hrs of strong sun, while maxing out the 5,600 W input cuts that to 1.4 hrs. To fully offset the Antminer S21 ASIC Hydro/Air Miner (240V PDU) at a 50% duty cycle (1,750 W average) during daylight you need roughly 2,200 W of panels, which this unit can accept.

5. Frequently Asked Questions

Can the EcoFlow Delta Pro Ultra (1 Inverter + 1 Battery) run a Antminer S21 ASIC Hydro/Air Miner (240V PDU)?

Yes. The EcoFlow Delta Pro Ultra (1 Inverter + 1 Battery) delivers 7,200 W continuous and 10,800 W surge, covering the Antminer S21 ASIC Hydro/Air Miner (240V PDU)'s 3,500 W running and 3,800 W start-up draw at 49% inverter utilization.

How long will the EcoFlow Delta Pro Ultra (1 Inverter + 1 Battery) run a Antminer S21 ASIC Hydro/Air Miner (240V PDU)?

With 6,144 Wh of capacity and 85% inverter efficiency, expect about 1.5 hrs of continuous operation and 3.0 hrs at a 50% duty cycle. Adding solar input during the day extends this further.

What breaker and wire size do I need to connect a Antminer S21 ASIC Hydro/Air Miner (240V PDU) to the EcoFlow Delta Pro Ultra (1 Inverter + 1 Battery)?

In the US, 3,500 W at 240 V is 14.6 A; applying the NEC 125% continuous-load rule gives 18.2 A, so use a 20 A breaker and 12 AWG copper for runs up to 25 ft (0.6% voltage drop). In 230 V markets the load draws 15.2 A, protected by a 16 A MCB on 1.5 mm² cable for runs up to 7.5 m. Receptacle: NEMA L6-30P / C19 PDU (US) or IEC 60309 16A Commando / Schuko 16A (UK/EU/AU).

How long does it take to recharge the EcoFlow Delta Pro Ultra (1 Inverter + 1 Battery) with solar panels?

With an 800 W array and an 80% real-world harvest factor, a full recharge takes about 9.6 hrs of peak sun (2.1 days at 4.5 peak-sun-hours). At its maximum 5,600 W solar input it drops to 1.4 hrs.

Methodology & safety note

Specifications come from manufacturer datasheets in our open dataset; ampacity and resistance values follow NEC Table 310.16 and Chapter 9 Table 8, and BS 7671 Appendix 4. Calculations assume copper conductors, 30 °C ambient and no bundling derating. Inverter-to-panel connections require a listed transfer switch or interlock to prevent back-feeding the grid. These results are an engineering estimate, not a substitute for a licensed electrician and local permit. See our methodology and safety disclaimer.

Status dots show the North American verdict: compatible, conditional, not compatible.

Other loads on the EcoFlow Delta Pro Ultra (1 Inverter + 1 Battery)

All 50 loads on the EcoFlow Delta Pro Ultra (1 Inverter + 1 Battery) →

Other power stations for the Antminer S21 ASIC Hydro/Air Miner (240V PDU)

Compare every source for this load →

More Medical, IT & Critical Loads on the EcoFlow Delta Pro Ultra (1 Inverter + 1 Battery)